5.1 All cable should be Heat Resistant, and suitable for 230V 50Hz supply.
5.2 The Heat Bank Thermal Store controls require connection to a fused 3A 230VAC 50Hz electrical supply to BS.1362. The unit is fitted with a 12 Terminal Junction Box, into which this supply should be taken.  The connection between the flow switch and pump is made within the pump.

 

5.3 Wire the Immersion Heater to a suitable switched supply, fused rated to 16 amp.
5.4 Check the Immersion Heater Thermostat is set to 80°C.
6 FILLING.
6.1 IMPORTANT: SYSTEMS SHOULD BE FLUSHED AND PROTECTED IN ACCORDANCE WITH BS7593-1992. Please check Boiler and other Primary Equipment's Installation Instructions prior to filling.
6.2 It is important that SENTINEL X100 Inhibitor is used to protect the Heat Bank Thermal Store. 
Use 1 litre per 100 litres of stored water.
Label the unit as protected with the label provided.
Contact Betz Dearborn direct for method statements on 0151 424 5351
Alternatively contact Fernox on 01799 550811
.
6.3 IMPORTANT: The Primary System should be fully flushed and an inhibitor, suitable for the purpose, used to protect both the primary and the Heat Bank Thermal Store systems. Betz Dearborn SENTINEL X300 should be used to flush the Primary System prior to filling new systems. Use SENTINEL X400 for existing systems. Please contact Betz Dearborn direct for method statements on 0151 424 5351, or alternatively contact Fernox on 01799 550811.
6.4 Stowaway Heat Bank Thermal Stores are filled using the Filling Loop provided.